SPAU 140 C | ABB | Synchro-Check Relay SPAU140C
Overview
- Model: SPAU 140 C
- Type: Synchro-Check Relay
- Function: Checks closing conditions of two separate circuit breakers
- Operation Stages: Two identical stages for synchro-check and voltage-check
Features
- Operation Modes: Continuous and command mode
- Display: Numerical display of setting values, measured values, and recorded data
- Self-Diagnostics: Continuous auto-diagnostic supervision
- Interface: Serial interface for SPA bus connection
- Software: Supports parameterization, reading values, events, and storing readings
- Integration: Part of ABB’s SPACOM and Panorama systems
- Certification: CE marking for EMC compliance
Energizing Inputs
- Rated Voltage: 100 V or 110 V
- Continuous Voltage Withstand: 2.0 × Un
- Burden: <0.5 VA
- Frequency Range: 45…65 Hz
- Rated Frequency: 50 Hz or 60 Hz (according to order)
Output Contact Ratings
- Contact Types: Heavy-duty and signalling
- Rated Voltage: 250 V AC/DC
-
Thermal Withstand Capability:
- Carry continuously: 5 A
- Make and carry for 0.5 s: 30 A (heavy-duty), 10 A (signalling)
- Make and carry for 3 s: 15 A (heavy-duty), 8 A (signalling)
-
Breaking Capacity:
- 220 V DC: 1 A (heavy-duty), 0.15 A (signalling)
- 110 V DC: 3 A (heavy-duty), 0.25 A (signalling)
- 48 V DC: 5 A (heavy-duty), 1 A (signalling)
- Contact Material: AgCdO₂
Control Inputs
- Control Voltage Level: 18…265 V DC or 80…265 V AC
- Typical Control Current: 2…20 mA
Data Communication
- Transmission Mode: Fibre-optic serial bus
- Data Code: ASCII
- Transfer Rates: 4800 or 9600 Bd
-
Bus Connection Modules:
- Powered from external power source for plastic core cables (SPA-ZC 17BB)
- Powered from host relay for plastic core cables (SPA-ZC 21BB)
Auxiliary Supply Modules
-
Supply Module: SPTU 240R4 (80…265 V AC/DC)
- Power Consumption: ~5 W (quiescent), ~7 W (operation)
- Supply Module: SPTU 48R4 (18…80 V DC)
SPAU 140 C | ABB | Synchro-Check Relay SPAU140C
Current product
Current
Vendor:
ABB
SPAU 140 C | ABB | Synchro-Check Relay SPAU140C
Regular price
$222.00
Sale price
$222.00
Regular price
$554.00
Options
Descriptions
Overview
- Model: SPAU 140 C
- Type: Synchro-Check Relay
- Function: Checks closing conditions of two separate circuit breakers
- Operation Stages: Two identical stages for synchro-check and voltage-check
Features
- Operation Modes: Continuous and command mode
- Display: Numerical display of setting values, measured values, and recorded data
- Self-Diagnostics: Continuous auto-diagnostic supervision
- Interface: Serial interface for SPA bus connection
- Software: Supports parameterization, reading values, events, and storing readings
- Integration: Part of ABB’s SPACOM and Panorama systems
- Certification: CE marking for EMC compliance
Energizing Inputs
- Rated Voltage: 100 V or 110 V
- Continuous Voltage Withstand: 2.0 × Un
- Burden: <0.5 VA
- Frequency Range: 45…65 Hz
- Rated Frequency: 50 Hz or 60 Hz (according to order)
Output Contact Ratings
- Contact Types: Heavy-duty and signalling
- Rated Voltage: 250 V AC/DC
-
Thermal Withstand Capability:
- Carry continuously: 5 A
- Make and carry for 0.5 s: 30 A (heavy-duty), 10 A (signalling)
- Make and carry for 3 s: 15 A (heavy-duty), 8 A (signalling)
-
Breaking Capacity:
- 220 V DC: 1 A (heavy-duty), 0.15 A (signalling)
- 110 V DC: 3 A (heavy-duty), 0.25 A (signalling)
- 48 V DC: 5 A (heavy-duty), 1 A (signalling)
- Contact Material: AgCdO₂
Control Inputs
- Control Voltage Level: 18…265 V DC or 80…265 V AC
- Typical Control Current: 2…20 mA
Data Communication
- Transmission Mode: Fibre-optic serial bus
- Data Code: ASCII
- Transfer Rates: 4800 or 9600 Bd
-
Bus Connection Modules:
- Powered from external power source for plastic core cables (SPA-ZC 17BB)
- Powered from host relay for plastic core cables (SPA-ZC 21BB)
Auxiliary Supply Modules
-
Supply Module: SPTU 240R4 (80…265 V AC/DC)
- Power Consumption: ~5 W (quiescent), ~7 W (operation)
- Supply Module: SPTU 48R4 (18…80 V DC)