FTA-T-14| Honeywell| Field Termination Assembly
Description
The FTA-T-14 is a specialized field termination assembly (FTA) designed for fail-safe 0(4)-20 mA analog input applications. It interfaces between system interconnection cables (SICs) and external field wiring using screw terminals, providing a secure and organized connection for up to 16 channels.
Features
- Channels: 16 channels.
- Protection: Fail-safe design with fuses.
- Termination: Screw terminals for reliable connections.
- Mounting: DIN rail mountable.
- Approvals: CE, UL.
Technical Specifications
- Type Number: FTA-T-14
-
Power Requirements:
- Maximum voltage: 36 Vac / 50 Vdc (overvoltage category 3)
- Maximum voltage: 125 Vac / 150 Vdc (overvoltage category 2)
- Number of Channels: 16
-
Module Dimensions:
- Length: 145 mm (5.71 in)
- Width: 70 mm (2.76 in)
- Height: 65 mm (2.56 in)
- DIN Rail Length: 146 mm (5.75 in)
-
Fuse Rating:
- Type: 250 mA slow-acting
- Dimensions: 5 x 20 mm (0.2 x 0.79 in) or 5 x 25 mm (0.2 x 0.98 in)
-
Termination:
- Max. wire diameter: 2.5 mm² (AWG 14)
- Strip length: 7 mm (0.28 in)
- Tightening torque: 0.5 Nm (0.37 ft-lb)
-
Connections:
- SIC connector: 1FF x 16 (1 connector of 16 signals, with one fuse per 8 signals)
- Field terminals: 16 groups of 4 screw terminals with 2 groups of 2 screw terminals for external power plus 2 earth screw terminals (T64/T)
FTA-T-14| Honeywell| Field Termination Assembly
FTA-T-14| Honeywell| Field Termination Assembly
Description
The FTA-T-14 is a specialized field termination assembly (FTA) designed for fail-safe 0(4)-20 mA analog input applications. It interfaces between system interconnection cables (SICs) and external field wiring using screw terminals, providing a secure and organized connection for up to 16 channels.
Features
- Channels: 16 channels.
- Protection: Fail-safe design with fuses.
- Termination: Screw terminals for reliable connections.
- Mounting: DIN rail mountable.
- Approvals: CE, UL.
Technical Specifications
- Type Number: FTA-T-14
-
Power Requirements:
- Maximum voltage: 36 Vac / 50 Vdc (overvoltage category 3)
- Maximum voltage: 125 Vac / 150 Vdc (overvoltage category 2)
- Number of Channels: 16
-
Module Dimensions:
- Length: 145 mm (5.71 in)
- Width: 70 mm (2.76 in)
- Height: 65 mm (2.56 in)
- DIN Rail Length: 146 mm (5.75 in)
-
Fuse Rating:
- Type: 250 mA slow-acting
- Dimensions: 5 x 20 mm (0.2 x 0.79 in) or 5 x 25 mm (0.2 x 0.98 in)
-
Termination:
- Max. wire diameter: 2.5 mm² (AWG 14)
- Strip length: 7 mm (0.28 in)
- Tightening torque: 0.5 Nm (0.37 ft-lb)
-
Connections:
- SIC connector: 1FF x 16 (1 connector of 16 signals, with one fuse per 8 signals)
- Field terminals: 16 groups of 4 screw terminals with 2 groups of 2 screw terminals for external power plus 2 earth screw terminals (T64/T)