Emerson | DeltaV | KL1604X1-BA1 | Safety Isolation Port (Copper)
KL1604X1-BA1 Safety Isolation Port (Copper)
Hazardous Atmosphere Certifications
- II 3G Ex ec IIC Gc
- FM19ATEX0173U
- IECEx FMG 19.0019U
- FM21UKEX0017U
- CL. I Div. 2 GP. A,B,C,D
- CL. I Zone 2 AEx/Ex ec IIC Gc
- FM17CA0145U
- FM17US0286U
Power Specifications
- Input power: +5.0 VDC at 200 mA
Environmental Specifications
- Ambient Temperature: -40 °C to +70 °C
- Shock: 10g ½ Sinewave for 11msec
- Vibration: 1mm Peak to Peak from 2 to 13.2Hz; 0.7g from 13.2 to 150Hz
- Airborne Contaminants: ISA-S71.04 –1985 Airborne Contaminants Class G3
- Relative Humidity: 5 to 95% Non-Condensing
Additional Information
- Note: Refer to the product label for serial number and location and date of manufacture.
- Warning: This product has specific instructions for installation, removal, and operation in hazardous areas. Refer to document 12P5403 "DeltaV Electronic Marshalling Digital Automation System (CHARM I/O Subsystem) Zone 2 Installation Instructions". Other installation instructions are available in the " DeltaV S-series and CHARMs Hardware Installation" manual.
- Removal and Insertion: This unit cannot be removed or inserted with system power energized unless the area is known to be non-hazardous.
- Maintenance and Adjustment: This unit contains no user serviceable parts and should not be disassembled for any reason. Calibration is not required.
Emerson | DeltaV | KL1604X1-BA1 | Safety Isolation Port (Copper)
Current product
Current
Vendor:
Delta V
Emerson | DeltaV | KL1604X1-BA1 | Safety Isolation Port (Copper)
Regular price
$230.00
Sale price
$230.00
Regular price
$350.00
Options
Descriptions
KL1604X1-BA1 Safety Isolation Port (Copper)
Hazardous Atmosphere Certifications
- II 3G Ex ec IIC Gc
- FM19ATEX0173U
- IECEx FMG 19.0019U
- FM21UKEX0017U
- CL. I Div. 2 GP. A,B,C,D
- CL. I Zone 2 AEx/Ex ec IIC Gc
- FM17CA0145U
- FM17US0286U
Power Specifications
- Input power: +5.0 VDC at 200 mA
Environmental Specifications
- Ambient Temperature: -40 °C to +70 °C
- Shock: 10g ½ Sinewave for 11msec
- Vibration: 1mm Peak to Peak from 2 to 13.2Hz; 0.7g from 13.2 to 150Hz
- Airborne Contaminants: ISA-S71.04 –1985 Airborne Contaminants Class G3
- Relative Humidity: 5 to 95% Non-Condensing
Additional Information
- Note: Refer to the product label for serial number and location and date of manufacture.
- Warning: This product has specific instructions for installation, removal, and operation in hazardous areas. Refer to document 12P5403 "DeltaV Electronic Marshalling Digital Automation System (CHARM I/O Subsystem) Zone 2 Installation Instructions". Other installation instructions are available in the " DeltaV S-series and CHARMs Hardware Installation" manual.
- Removal and Insertion: This unit cannot be removed or inserted with system power energized unless the area is known to be non-hazardous.
- Maintenance and Adjustment: This unit contains no user serviceable parts and should not be disassembled for any reason. Calibration is not required.