DX561 | ABB | Digital Input/Output Module

SKU: DX561
  • Manufacturer: ABB

  • Product No.: DX561

  • Condition:In stock

  • Product Type: Digital Input/Output Module

  • Product Origin: Sweden

  • Payment:T/T, Western Union

  • Weight: 120g

  • Shipping port: Xiamen

  • Warranty: 12 months

Ordering Information

  • Part Number: 1TNE 968 902 R2301
  • Description: DX561, Digital Input/Output Module, 8 DI 24 V DC, 8 DO 24 V DC, Transistor Output
  • Product Life Cycle Phase: Active

Technical Data

  • Process Supply Voltage UP: Rated value 24 V DC
  • Connections:
    • Terminal 19 for UP (+24 V DC)
    • Terminal 20 for ZP (0 V DC)
  • Current Consumption via UP Terminal:
    • 5 mA + max. 0.5 A per output
  • Max. Ripple: 5%
  • Inrush Current: 0.000002 A²s
  • Protection Against Reversed Voltage: Yes
  • Rated Protection Fuse for UP:
    • Recommended: The outputs must be protected by a 3 A fast-acting fuse
  • Current Consumption from 24 V DC Power Supply at L+/UP and M/ZP Terminals of the CPU/Communication Interface Module:
    • Approx. 10 mA
  • Galvanic Isolation: Yes, between the input group and the output group and the rest of the module
  • Isolated Groups: 2 groups (1 group for 8 input channels, 1 group for 8 output channels)
  • Surge-Voltage (Max.): 35 V DC for 0.5 s
  • Max. Power Dissipation Within the Module: 2.3 W
  • Weight: Approx. 120 g
  • Mounting Position: Horizontal or vertical
  • Cooling: Must not be hindered by cable ducts or other parts in the control cabinet. Natural convection cooling required.

Digital Input Specifications

  • Number of Channels per Module: 8
  • Distribution of Channels into Groups: 1 group for 8 channels
  • Connections of the Channels I0 ... I7: Terminals 2 ... 9
  • Reference Potential for Channels I0 ... I7: Terminal 1
  • Indication of Input Signals:
    • 1 yellow LED per channel
    • LED on when the input signal is high (Signal 1)
  • Monitoring Point of Input Indicator LED: Part of the input circuitry
  • Input Type According to EN 61131-2:
    • Type 1 source
    • Type 1 sink
  • Input Signal Range:
    • Signal 0: -5 V ... +3 V
    • Undefined Signal: -15 V ... +5 V
    • Signal 1: -30 V ... -15 V
  • Ripple with Signal 0: -5 V ... +3 V
  • Ripple with Signal 1: -30 V ... -15 V
  • Input Current per Channel:
    • Input Voltage +24 V: Typ. 5 mA
    • Input Voltage +5 V: Typ. 1 mA
    • Input Voltage +15 V: > 2.5 mA
    • Input Voltage +30 V: < 8 mA
  • Max. Permissible Leakage Current (at 2-wire Proximity Switches): 1 mA
  • Input Delay (0 -> 1 or 1 -> 0): Typ. 8 ms
  • Input Data Length: 1 byte
  • Max. Cable Length (Shielded): 500 m
  • Max. Cable Length (Unshielded): 300 m

Digital Output Specifications

  • Number of Channels per Module: 8 transistor outputs (24 V DC, 0.5 A max.)
  • Distribution of Channels into Groups: 1 group of 8 channels
  • Connection of Channels O0 ... O7: Terminals 11 ... 18
  • Reference Potential for Channels O0 ... O7: Terminal 20 (negative pole of the process voltage, name ZP)
  • Common Power Supply Voltage:
    • Terminal 19 (positive pole of the process voltage, name UP)
  • Indication of Output Signals:
    • 1 yellow LED per channel
    • LED on when output signal is high (Signal 1) and module is powered via I/O bus
  • Monitoring Point of Output Indicator LED: Controlled together with transistor
  • Mode of Operation: Non-latching type
  • Max. Output Voltage at Signal 1: 20 V DC at max. current consumption
  • Output Delay:
    • 0 to 1: 50 µs
    • 1 to 0: 200 µs
  • Output Data Length: 1 byte
  • Rated Output Current per Channel (Max.): 0.5 A at UP 24 V DC
  • Rated Output Current per Group (Max.): 4 A
  • Rated Output Current (All Channels Together, Max.): 4 A
  • Lamp Load (Max.): 5 W
  • Max. Leakage Current with Signal 0: 0.5 mA
  • Output Type: Non-protected
  • Protection Type: External fuse on each channel
  • Rated Protection Fuse (for Each Channel): 3 A fast
  • Demagnetization when Inductive Loads are Switched Off: Must be performed externally according to driven load specification
  • Switching Frequencies:
    • With Inductive Loads: Max. 0.5 Hz
    • With Lamp Loads: Max. 11 Hz at max. 5 W
  • Short-Circuit-Proof / Overload-Proof: No, should be provided by an external fuse or circuit breaker
  • Overload Message: No
  • Output Current Limitation: No
  • Resistance to Feedback Against 24 V DC: No
  • Connection of 2 Outputs in Parallel: Not possible
  • Max. Cable Length (Shielded): 500 m
  • Max. Cable Length (Unshielded): 150 m
Order and Warranty Information

Terms of Purchase and Returns

Detailed guidelines on minimum order quantity, delivery times, payment options, warranty, and return policies.

We gladly accept bulk orders, with a minimum order quantity of just one unit.

Upon request, we can provide all necessary documents, including Certificates of Origin/Conformance and other required export paperwork.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% payable before shipment. For RMB transfers, please contact us if you have an agent in China.

All new and original items come with a standard one-year warranty. For extended warranty options, feel free to contact us for pricing details.

We prioritize your satisfaction. If you need to return an item, it must be done within 30 days of purchase. The product must be unused, unopened, and in its original packaging, including all accessories. Refunds will be processed within 5-7 business days of receiving the return. Please note, shipping and handling charges are non-refundable.

Product comparison