DI572 | ABB | Digital Input Module
Ordering
- Part no.: 1SAP 230 500 R0000
- Description: DI572, digital input module, 16 DI, 100 V AC ... 240 V AC
- Product life cycle phase: Active
Technical
- Galvanic isolation: Yes, between the input groups and the rest of the module
- Isolated groups: 2 (8 channels per group)
- Current consumption from 24 V DC power supply: Ca. 10 mA
- Max. power dissipation within the module: 6 W
- Weight: Ca. 222 g
- Mounting position: Horizontal or vertical
- Cooling: The natural convection cooling must not be hindered by cable ducts or other parts in the control cabinet
Digital Inputs
- Number of channels per module: 16 AC inputs (100-240 V AC)
- Distribution of the channels into groups: 2 (8 channels per group)
- Input voltage range: 0 V AC ... 264 V AC (47 Hz ... 63 Hz)
-
Input current per channel (typically at +25 °C):
- < 3 mA (at 40 V AC)
- > 6 mA (at 164 V AC)
- > 8 mA (at 240 V AC)
- < 3 mA (at 40 V AC)
- Connections of the channels I0..I7: Terminals 1...8
- Connections of the channels I8...I15: Terminals 10...17
- Reference potential for the channels I0...I7: Terminal 9
- Reference potential for the channels I8...I15: Terminal 18
- Indication of the input signals: 1 yellow LED per channel. The LED is on when the input signal is high (signal 1)
Input Type
- Type: Type 1 according to EN 61131-2
-
Input signal range:
- Signal 0 (max.): 40 V AC
- Undefined signal: 40 V AC < U < 79 V AC
- Signal 1 (min.): 79 V AC
-
Input delay:
- Signal 0 -> 1: Typ. 24 ms
- Signal 1 -> 0: Typ. 24 ms
- Input data length: 2 bytes
- Max. permissible leakage current (at 2-wire proximity switches): 1 mA
-
Max. cable length:
- Shielded: 1000 m
- Unshielded: 600 m
DI572 | ABB | Digital Input Module
Current product
Current
Vendor:
ABB
DI572 | ABB | Digital Input Module
Regular price
$215.00
Sale price
$215.00
Regular price
$543.00
Options
Descriptions
Ordering
- Part no.: 1SAP 230 500 R0000
- Description: DI572, digital input module, 16 DI, 100 V AC ... 240 V AC
- Product life cycle phase: Active
Technical
- Galvanic isolation: Yes, between the input groups and the rest of the module
- Isolated groups: 2 (8 channels per group)
- Current consumption from 24 V DC power supply: Ca. 10 mA
- Max. power dissipation within the module: 6 W
- Weight: Ca. 222 g
- Mounting position: Horizontal or vertical
- Cooling: The natural convection cooling must not be hindered by cable ducts or other parts in the control cabinet
Digital Inputs
- Number of channels per module: 16 AC inputs (100-240 V AC)
- Distribution of the channels into groups: 2 (8 channels per group)
- Input voltage range: 0 V AC ... 264 V AC (47 Hz ... 63 Hz)
-
Input current per channel (typically at +25 °C):
- < 3 mA (at 40 V AC)
- > 6 mA (at 164 V AC)
- > 8 mA (at 240 V AC)
- < 3 mA (at 40 V AC)
- Connections of the channels I0..I7: Terminals 1...8
- Connections of the channels I8...I15: Terminals 10...17
- Reference potential for the channels I0...I7: Terminal 9
- Reference potential for the channels I8...I15: Terminal 18
- Indication of the input signals: 1 yellow LED per channel. The LED is on when the input signal is high (signal 1)
Input Type
- Type: Type 1 according to EN 61131-2
-
Input signal range:
- Signal 0 (max.): 40 V AC
- Undefined signal: 40 V AC < U < 79 V AC
- Signal 1 (min.): 79 V AC
-
Input delay:
- Signal 0 -> 1: Typ. 24 ms
- Signal 1 -> 0: Typ. 24 ms
- Input data length: 2 bytes
- Max. permissible leakage current (at 2-wire proximity switches): 1 mA
-
Max. cable length:
- Shielded: 1000 m
- Unshielded: 600 m