Honeywell | TC-IDD321 | Experion LS I/O
Overview
The Honeywell TC-IDD321 is an Experion LS I/O module designed for industrial control systems, providing 32 digital input points for reliable signal processing.
Specifications
- Number of Inputs: 32 (16 points/common)
- Nominal Input Voltage: 24 VDC
- On-State Current (Minimum): 2 mA
- Off-State Voltage (Maximum): 5 V
- Off-State Current (Maximum): 1.5 mA
- Power Dissipation: 6.1 W max
- Input Compatibility: IEC Type 1+
- Isolation Voltage (Channel to Channel): 100% tested at 1500 VDC for 1 second
- Isolation Voltage (User to System): 100% tested at 1500 VDC for 1 second
- Connection Terminal Blocks: TC-TBNH, 36-position terminal block
Performance Features
-
Input Delay Time:
- Off to On: Programmable filter (0 ms, 1 ms, or 2 ms), Hardware delay 1 ms max
- On to Off: Programmable filter (0 ms, 1 ms, 2 ms, 9 ms, or 18 ms), Hardware delay 1 ms max
- Short/Inrush Current: 250 mA peak (decaying to <37% in 22 ms, without activation)
- Backplane Current: See Module Power Consumption Data
Honeywell | TC-IDD321 | Experion LS I/O
Текущий продукт
Текущий
Продавец:
Honeywell
Honeywell | TC-IDD321 | Experion LS I/O
Обычная цена
$238.00
Цена продажи
$238.00
Обычная цена
$560.00
Параметры
Описания
Overview
The Honeywell TC-IDD321 is an Experion LS I/O module designed for industrial control systems, providing 32 digital input points for reliable signal processing.
Specifications
- Number of Inputs: 32 (16 points/common)
- Nominal Input Voltage: 24 VDC
- On-State Current (Minimum): 2 mA
- Off-State Voltage (Maximum): 5 V
- Off-State Current (Maximum): 1.5 mA
- Power Dissipation: 6.1 W max
- Input Compatibility: IEC Type 1+
- Isolation Voltage (Channel to Channel): 100% tested at 1500 VDC for 1 second
- Isolation Voltage (User to System): 100% tested at 1500 VDC for 1 second
- Connection Terminal Blocks: TC-TBNH, 36-position terminal block
Performance Features
-
Input Delay Time:
- Off to On: Programmable filter (0 ms, 1 ms, or 2 ms), Hardware delay 1 ms max
- On to Off: Programmable filter (0 ms, 1 ms, 2 ms, 9 ms, or 18 ms), Hardware delay 1 ms max
- Short/Inrush Current: 250 mA peak (decaying to <37% in 22 ms, without activation)
- Backplane Current: See Module Power Consumption Data