Here are the technical specifications for the Yokogawa SAI143-H63 Analog Input Module:
- Module Type: Current Input Module (SAI143-H63)
- Number of Input Channels: 16 channels (module isolation)
- Rated Input Range: 4 to 20 mA
- Permissible Input Range: 0 to 25 mA
-
Input Impedance During Power-ON:
- Voltage drop in the input protection circuit inside the module: 250 Ω + Current value
- Input Impedance During Power-OFF: 500 kΩ minimum
-
Rated Accuracy:
- SAI143-S: ±16 μA (Input range 1 to 23 mA)
- SAI143-H: ±16 μA (Input range 0.05 to 23 mA)
- Data Update Frequency: 40 ms
- Temperature Drift: ±16 μA/10 °C
-
Transmitter Power Supply:
- Minimum: 16.15 V (at 20 mA)
- Maximum: 26.4 V (at 0 mA) (Output current limit: 25 mA)
- 2/4-Wire Setting: Individual channel setting changed by setting pins
- Withstand Voltage: 1.5 kV AC between input signal and system for 1 minute
-
Maximum Current Consumption:
- 5 V system: 320 mA
- 24 V system: 550 mA
-
Weight:
- Approx. 0.34 kg (For pressure clamp terminal block or MIL cable)
- Approx. 0.39 kg (With signal cable interface adapter)
- External Connection: Pressure clamp terminal, MIL cable, Dedicated signal cable
- Support for PRM: Available (SAI143-H)
- Transmitter Power Supply ON/OFF Function: Available in 2-wire setting for all 16 channels simultaneously
Yokogawa SAI143-H63 | Analog Input Module | Good Quality
Current product
Current
Vendor:
Yokogawa
Yokogawa SAI143-H63 | Analog Input Module | Good Quality
Regular price
$200.00
Sale price
$200.00
Regular price
$300.00
Options
Descriptions
Description
Here are the technical specifications for the Yokogawa SAI143-H63 Analog Input Module:
- Module Type: Current Input Module (SAI143-H63)
- Number of Input Channels: 16 channels (module isolation)
- Rated Input Range: 4 to 20 mA
- Permissible Input Range: 0 to 25 mA
-
Input Impedance During Power-ON:
- Voltage drop in the input protection circuit inside the module: 250 Ω + Current value
- Input Impedance During Power-OFF: 500 kΩ minimum
-
Rated Accuracy:
- SAI143-S: ±16 μA (Input range 1 to 23 mA)
- SAI143-H: ±16 μA (Input range 0.05 to 23 mA)
- Data Update Frequency: 40 ms
- Temperature Drift: ±16 μA/10 °C
-
Transmitter Power Supply:
- Minimum: 16.15 V (at 20 mA)
- Maximum: 26.4 V (at 0 mA) (Output current limit: 25 mA)
- 2/4-Wire Setting: Individual channel setting changed by setting pins
- Withstand Voltage: 1.5 kV AC between input signal and system for 1 minute
-
Maximum Current Consumption:
- 5 V system: 320 mA
- 24 V system: 550 mA
-
Weight:
- Approx. 0.34 kg (For pressure clamp terminal block or MIL cable)
- Approx. 0.39 kg (With signal cable interface adapter)
- External Connection: Pressure clamp terminal, MIL cable, Dedicated signal cable
- Support for PRM: Available (SAI143-H)
- Transmitter Power Supply ON/OFF Function: Available in 2-wire setting for all 16 channels simultaneously