Triconex |9565-810|Digital Input Termination Panel
Description
The 9565-810 is a termination panel designed for use with 24/48 VDC digital input modules in Tricon v9–v10 systems. It provides 32 input points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a fuse with a blown-fuse indicator, ensuring reliable operation in industrial environments.
Features
- Compatible with 24/48 VDC digital input modules.
- 32 input points per panel.
- Commoned power terminals.
- Built-in blown-fuse indicators.
- Supports 64-point modules (requires two panels).
Technical Specifications
Input Points: 32
Power Terminals: Commoned (PWR+ and PWR–)
Leakage Current per Point: Maximum 3.5 mA, Typical 2.0 mA
Fuse Protection: 1A, slow-blow fuse with LED indicator
Operating Voltage: 24/48 VDC
Modules Compatible:
- 3504E (24/48 VDC, commoned, high-density, DC-coupled, 1A, slow TMR)
Field Wiring:
- Designed for 48V applications.
- Each input point must be connected to the field device and the common power terminal.
- Fuses protect against overcurrent conditions, with LEDs indicating blown fuses.
Environmental Conditions:
- Operating Temperature Range: 0 to 60°C
- Storage Temperature Range: -40°C to 85°C
- Humidity (non-condensing): 0 to 95%
Installation:
- Torque Specifications for Field Wiring Terminals: 4.425–5.310 lbf in (0.5–0.6 Nm)
- Torque Specifications for Power Terminals: 4.425–5.310 lbf in (0.5–0.6 Nm)
Triconex |9565-810|Digital Input Termination Panel



Triconex |9565-810|Digital Input Termination Panel
Description
The 9565-810 is a termination panel designed for use with 24/48 VDC digital input modules in Tricon v9–v10 systems. It provides 32 input points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a fuse with a blown-fuse indicator, ensuring reliable operation in industrial environments.
Features
- Compatible with 24/48 VDC digital input modules.
- 32 input points per panel.
- Commoned power terminals.
- Built-in blown-fuse indicators.
- Supports 64-point modules (requires two panels).
Technical Specifications
Input Points: 32
Power Terminals: Commoned (PWR+ and PWR–)
Leakage Current per Point: Maximum 3.5 mA, Typical 2.0 mA
Fuse Protection: 1A, slow-blow fuse with LED indicator
Operating Voltage: 24/48 VDC
Modules Compatible:
- 3504E (24/48 VDC, commoned, high-density, DC-coupled, 1A, slow TMR)
Field Wiring:
- Designed for 48V applications.
- Each input point must be connected to the field device and the common power terminal.
- Fuses protect against overcurrent conditions, with LEDs indicating blown fuses.
Environmental Conditions:
- Operating Temperature Range: 0 to 60°C
- Storage Temperature Range: -40°C to 85°C
- Humidity (non-condensing): 0 to 95%
Installation:
- Torque Specifications for Field Wiring Terminals: 4.425–5.310 lbf in (0.5–0.6 Nm)
- Torque Specifications for Power Terminals: 4.425–5.310 lbf in (0.5–0.6 Nm)