Triconex|PI3381|Pulse Input Module
- Points: 6, channel-isolated, commoned ground
- Input Type: Differential
- Sensor Compatibility: Magnetic, active, open collector
- Maximum Operating Voltage: ±33 V DC
-
Minimum Operating Voltage:
- Differential: 500 mV P-P, 2 Hz to 32,000 Hz; 1 V P-P, 0.5 Hz to 2 Hz
- Single-ended: 1 V P-P, 2 Hz to 32,000 Hz; 2 V P-P, 0.5 Hz to 2 Hz
- Speed Range: 0 to 32,000 RPM
- Input Frequency Range: 0.5 Hz to 32 kHz
- Duty Cycle: 20% to 80%, or 10 µs minimum pulse width
- Maximum Continuous Slew Rate: 4,000 Hz/sec with 60 gear teeth
- Maximum Continuous RPM Slew Rate: 4,000 RPM/sec with 60 gear teeth
- Number of Gear Teeth: 1–255
- Termination Resistor: Baseplate configurable
- Pull-up Resistor: Baseplate configurable
- Resolution: 24 bits
-
Absolute Error:
- ±0.01% (2,000 to 32,000 Hz)
- ±0.1% (0.5 to 2,000 Hz)
- Measurement Algorithm: Gear multiple tracking
- Diagnostic: Precision reference test
- Minimum Scan Update Rate: 20 ms
- Functional-to-Protective-Earth Isolation: 500 V DC, minimum
- Functional-to-Functional-Earth (Logic) Isolation: 800 V DC, minimum
Triconex|PI3381|Pulse Input Module
Current product
Current
Vendor:
Triconex
Triconex|PI3381|Pulse Input Module
Regular price
$100.00
Sale price
$100.00
Regular price
$300.00
Options
Descriptions
- Points: 6, channel-isolated, commoned ground
- Input Type: Differential
- Sensor Compatibility: Magnetic, active, open collector
- Maximum Operating Voltage: ±33 V DC
-
Minimum Operating Voltage:
- Differential: 500 mV P-P, 2 Hz to 32,000 Hz; 1 V P-P, 0.5 Hz to 2 Hz
- Single-ended: 1 V P-P, 2 Hz to 32,000 Hz; 2 V P-P, 0.5 Hz to 2 Hz
- Speed Range: 0 to 32,000 RPM
- Input Frequency Range: 0.5 Hz to 32 kHz
- Duty Cycle: 20% to 80%, or 10 µs minimum pulse width
- Maximum Continuous Slew Rate: 4,000 Hz/sec with 60 gear teeth
- Maximum Continuous RPM Slew Rate: 4,000 RPM/sec with 60 gear teeth
- Number of Gear Teeth: 1–255
- Termination Resistor: Baseplate configurable
- Pull-up Resistor: Baseplate configurable
- Resolution: 24 bits
-
Absolute Error:
- ±0.01% (2,000 to 32,000 Hz)
- ±0.1% (0.5 to 2,000 Hz)
- Measurement Algorithm: Gear multiple tracking
- Diagnostic: Precision reference test
- Minimum Scan Update Rate: 20 ms
- Functional-to-Protective-Earth Isolation: 500 V DC, minimum
- Functional-to-Functional-Earth (Logic) Isolation: 800 V DC, minimum