140DRA84000 | SCHNEIDER | Relay Discrete Output Module

SKU: 140DRA84000
  • Manufacturer: SCHNEIDER

  • Product No.: 140DRA84000

  • Condition:In stock

  • Product Type: Relay Discrete Output Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 410g

  • Shipping port: Xiamen

  • Warranty: 12 months

Overview

The 140DRA84000 is a Relay Discrete Output Module for Schneider Electric's Modicon Quantum automation platform. This module provides 16 discrete relay outputs, offering versatile control for various industrial applications.

Specifications

  • Range: Modicon Quantum automation platform
  • Product Type: Relay Discrete Output Module
  • Discrete Output Number: 16

Electrical Characteristics

  • Contacts Type: 1 NO (Form A)

  • Discrete Output Voltage:

    • 20...250 V AC
    • 30...150 V DC
    • 5...30 V DC
  • Addressing Requirement: 1 output word

  • Minimum Load:

    • ≥ 50 mA at 20...250 V AC
    • ≥ 50 mA at 5...30 V DC
  • Maximum Load Current:

    • 1 A at 250/30 V AC/DC (1/8 hp, cos phi = 0.4)
    • 1 A at 250/30 V AC/DC (tungsten)
    • 2 A at 250/30 V AC/DC (resistive at 140 °F, 60 °C)
    • 300 mA at 30...50 V DC (resistive)
  • Surge Current: ≤ 10 A for 10 ms (capacitive)

  • Switching Capacity: 500 VA (resistive)

Performance

  • Response Time:

    • State 0 to State 1: ≤ 10 ms
    • State 1 to State 0: ≤ 20 ms
  • Mechanical Durability: 10,000,000 cycles

  • Electrical Durability:

    • 100,000 cycles at 100 mA (30...150 V DC, L/R = 10 ms)
    • 100,000 cycles at 2 A (30 V DC resistive)
    • 100,000 cycles at 30...150 V DC (interposing relay)
    • 100,000 cycles at 300 mA (30...150 V DC resistive)
    • 200,000 cycles at 2 A (250 V AC resistive)
    • 50,000 cycles at 500 mA (30...150 V DC resistive)

Protection & Isolation

  • Output Overvoltage Protection: Internal varistor (275 V)
  • Isolation Between Channels: 1780 Vrms AC for 1 minute
  • Isolation Between Channels and Bus:
    • 1780 Vrms AC for 1 minute
    • 2500 V DC for 1 minute

Power & Signaling

  • Power Dissipation: 5.5 W + (0.5 x the number of points on)
  • Bus Current Requirement: 1100 mA
  • Local Signaling:
    • 1 LED (green) for bus communication (Active)
    • 1 LED (red) for external fault detection
    • 16 LEDs (green) for input status

Environmental Conditions

  • Product Weight: 0.41 kg (0.9 lb)

  • Product Certifications:

    • ABS
    • C-Tick
    • FM Class 1 Division 2
    • GOST
  • Standards:

    • CSA C22.2 No 142
    • UL 508
  • Environmental Resistance:

    • Electrostatic Discharge: 4 kV contact (IEC 801-2), 8 kV on air (IEC 801-2)
    • Electromagnetic Fields: 9.14 V/yd (10 V/m) 80...2000 MHz (IEC 801-3)
  • Temperature Range:

    • Operating: 0...60 °C (32...140 °F)
    • Storage: -40...85 °C (-40...185 °F)
  • Relative Humidity: 95% without condensation

  • Operating Altitude: ≤ 5000 m (16,404.2 ft)

Order and Warranty Information

Terms of Purchase and Returns

Detailed guidelines on minimum order quantity, delivery times, payment options, warranty, and return policies.

We gladly accept bulk orders, with a minimum order quantity of just one unit.

Upon request, we can provide all necessary documents, including Certificates of Origin/Conformance and other required export paperwork.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% payable before shipment. For RMB transfers, please contact us if you have an agent in China.

All new and original items come with a standard one-year warranty. For extended warranty options, feel free to contact us for pricing details.

We prioritize your satisfaction. If you need to return an item, it must be done within 30 days of purchase. The product must be unused, unopened, and in its original packaging, including all accessories. Refunds will be processed within 5-7 business days of receiving the return. Please note, shipping and handling charges are non-refundable.

Product comparison