MTL Instruments | MTL4516 | Relay Module
- The MTLx516/C enables two safe-area loads to be controlled by a switch or proximity detector located in a hazardous area.
- The line-fault-detect (LFD) facility detects open or short circuit conditions in the field wiring and indicates them on the top of the module.
- Phase reversal for each channel is selected by a switch on the side of the module, and the output is provided by changeover relay contacts.
Specification
- Number of Channels: Two
-
Location of Switches:
- Zone 0, IIC, T6 hazardous area
- Div. 1, Group A hazardous location
-
Location of Proximity Detector:
- Zone 0, IIC, T4–6 hazardous area if suitably certified
- Div. 1, Group A hazardous location
-
Hazardous-Area Inputs:
- Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
- Voltage applied to sensor: 7 to 9V dc from 1kΩ ±10%
-
Input/Output Characteristics:
-
Normal Phase:
- Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
- Outputs open if input < 1.2mA (> 10kΩ in input circuit)
- Hysteresis: 200µA (650Ω) nominal
-
Line Fault Detection (LFD) (When Selected):
- User-selectable via switches on the side of the unit.
- Line faults are indicated by an LED for each channel.
- The channel output relay is de-energised if an input line fault is detected.
-
Open-Circuit Alarm:
- On if Iin < 50µA
- Off if Iin > 250µA
-
Short-Circuit Alarm:
- On if Rin < 100Ω
- Off if Rin > 360Ω
-
Note: Resistors must be fitted when using the LFD facility with a contact input:
- 500Ω to 1kΩ in series with switch
- 20kΩ to 25kΩ in parallel with switch
-
Normal Phase:
MTL Instruments | MTL4516 | Relay Module
Current product
Current
Vendor:
MTL
MTL Instruments | MTL4516 | Relay Module
Regular price
$230.00
Sale price
$230.00
Regular price
$350.00
Options
Descriptions
- The MTLx516/C enables two safe-area loads to be controlled by a switch or proximity detector located in a hazardous area.
- The line-fault-detect (LFD) facility detects open or short circuit conditions in the field wiring and indicates them on the top of the module.
- Phase reversal for each channel is selected by a switch on the side of the module, and the output is provided by changeover relay contacts.
Specification
- Number of Channels: Two
-
Location of Switches:
- Zone 0, IIC, T6 hazardous area
- Div. 1, Group A hazardous location
-
Location of Proximity Detector:
- Zone 0, IIC, T4–6 hazardous area if suitably certified
- Div. 1, Group A hazardous location
-
Hazardous-Area Inputs:
- Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
- Voltage applied to sensor: 7 to 9V dc from 1kΩ ±10%
-
Input/Output Characteristics:
-
Normal Phase:
- Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
- Outputs open if input < 1.2mA (> 10kΩ in input circuit)
- Hysteresis: 200µA (650Ω) nominal
-
Line Fault Detection (LFD) (When Selected):
- User-selectable via switches on the side of the unit.
- Line faults are indicated by an LED for each channel.
- The channel output relay is de-energised if an input line fault is detected.
-
Open-Circuit Alarm:
- On if Iin < 50µA
- Off if Iin > 250µA
-
Short-Circuit Alarm:
- On if Rin < 100Ω
- Off if Rin > 360Ω
-
Note: Resistors must be fitted when using the LFD facility with a contact input:
- 500Ω to 1kΩ in series with switch
- 20kΩ to 25kΩ in parallel with switch
-
Normal Phase: