DO571 | ABB | Digital Output Module
Ordering Data
- Part No.: 1TNE 968 902 R2202
- Description: DO571, digital output module, 8 DO, relay output
- Product Life Cycle Phase: Active
Technical Data
- Process Supply Voltage L+:
-
- Connections: Terminal 20 for L+ (+24 V DC). The negative pole is provided by the I/O bus.
- Rated Value: 24 V DC
- Current Consumption via L+: 50 mA
- Inrush Current (at Power-up): 0.0035 A²s
- Max. Ripple: 5 %
- Protection Against Reversed Voltage: Yes
- Rated Protection Fuse for UP: Recommended; the outputs must be protected by a 3 A fast-acting fuse
- Current Consumption from 24 V DC Power Supply at L+/UP and M/ZP Terminals of the CPU/Communication Interface Module: Ca. 5 mA
- Galvanic Isolation: Yes, between the output group and the rest of the module
- Isolated Groups: 2 (4 channels per group)
- Surge-Voltage (Max.): 35 V DC for 0.5 s
- Max. Power Dissipation within the Module: 2.0 W
- Weight: Ca. 150 g
- Mounting Position: Horizontal or vertical
- Cooling: The natural convection cooling must not be hindered by cable ducts or other parts in the control cabinet
- Technical Data of the Digital Outputs
- Number of Channels per Module: 8 normally-open relay outputs
- Distribution of the Channels into Groups: 2 (4 channels per group)
-
Connection of the Channels:
- O0 ... O3: Terminals 10 ... 13
- O4 ... O7: Terminals 15 ... 18
-
Reference Potential for the Channels:
- O0 ... O3: Terminal 14 (signal name R0 ... R3)
- O4 ... O7: Terminal 19 (signal name R4 ... R7)
- Relay Coil Power Supply: Terminal 20 (positive pole of the process supply voltage, signal name L+). The negative pole is provided by the I/O bus.
- Indication of the Output Signals: 1 yellow LED per channel; the LED is on when the output signal is high (signal 1) and the module is powered via the I/O bus
- Way of Operation: Non-latching type
-
Relay Output Voltage:
- Rated Value: 24 V DC / 24 V AC or 120/240 V AC
-
Output Delay:
- Switching 0 to 1 (Max.): Typ. 10 ms
- Switching 1 to 0 (Max.): Typ. 10 ms
- Output Data Length: 1 byte
-
Output Current:
- Rated Current per Channel (Max.):
- 2.0 A (24 V DC / 24 V AC / 48 V AC / 120 V AC / 240 V AC, only resistive loads)
- 2.0 A (24 V AC / 48 V AC / 120 V AC, only pilot duty)
- 1.5 A (240 V AC, only pilot duty)
- Rated Current per Group (Max.): 8 A
-
Lamp Load (Max.):
- 200 W (230 V AC), 30 W (24 V DC)
- Spark Suppression with Inductive AC Loads: Must be performed externally according to driven load specification
-
Switching Frequencies:
- With resistive loads: Max. 1 Hz
- With inductive loads: On Request
- With lamp loads: Max. 1 Hz
- Output Type: Non-protected
- Rated Protection Fuse: 5 A fast
- Short-Circuit-Proof / Overload-Proof: No, should be provided by an external fuse or circuit breaker
- Overload Message: No
- Output Current Limitation: No
- Connection of 2 Outputs in Parallel: Not possible
- Lifetime of Relay Contacts (Cycles): 100,000 at rated load
-
Max. Cable Length:
- Shielded: 500 m
- Unshielded: 150 m
DO571 | ABB | Digital Output Module
Current product
Current
Vendor:
ABB
DO571 | ABB | Digital Output Module
Regular price
$230.00
Sale price
$230.00
Regular price
$550.00
Options
Descriptions
Ordering Data
- Part No.: 1TNE 968 902 R2202
- Description: DO571, digital output module, 8 DO, relay output
- Product Life Cycle Phase: Active
Technical Data
- Process Supply Voltage L+:
-
- Connections: Terminal 20 for L+ (+24 V DC). The negative pole is provided by the I/O bus.
- Rated Value: 24 V DC
- Current Consumption via L+: 50 mA
- Inrush Current (at Power-up): 0.0035 A²s
- Max. Ripple: 5 %
- Protection Against Reversed Voltage: Yes
- Rated Protection Fuse for UP: Recommended; the outputs must be protected by a 3 A fast-acting fuse
- Current Consumption from 24 V DC Power Supply at L+/UP and M/ZP Terminals of the CPU/Communication Interface Module: Ca. 5 mA
- Galvanic Isolation: Yes, between the output group and the rest of the module
- Isolated Groups: 2 (4 channels per group)
- Surge-Voltage (Max.): 35 V DC for 0.5 s
- Max. Power Dissipation within the Module: 2.0 W
- Weight: Ca. 150 g
- Mounting Position: Horizontal or vertical
- Cooling: The natural convection cooling must not be hindered by cable ducts or other parts in the control cabinet
- Technical Data of the Digital Outputs
- Number of Channels per Module: 8 normally-open relay outputs
- Distribution of the Channels into Groups: 2 (4 channels per group)
-
Connection of the Channels:
- O0 ... O3: Terminals 10 ... 13
- O4 ... O7: Terminals 15 ... 18
-
Reference Potential for the Channels:
- O0 ... O3: Terminal 14 (signal name R0 ... R3)
- O4 ... O7: Terminal 19 (signal name R4 ... R7)
- Relay Coil Power Supply: Terminal 20 (positive pole of the process supply voltage, signal name L+). The negative pole is provided by the I/O bus.
- Indication of the Output Signals: 1 yellow LED per channel; the LED is on when the output signal is high (signal 1) and the module is powered via the I/O bus
- Way of Operation: Non-latching type
-
Relay Output Voltage:
- Rated Value: 24 V DC / 24 V AC or 120/240 V AC
-
Output Delay:
- Switching 0 to 1 (Max.): Typ. 10 ms
- Switching 1 to 0 (Max.): Typ. 10 ms
- Output Data Length: 1 byte
-
Output Current:
- Rated Current per Channel (Max.):
- 2.0 A (24 V DC / 24 V AC / 48 V AC / 120 V AC / 240 V AC, only resistive loads)
- 2.0 A (24 V AC / 48 V AC / 120 V AC, only pilot duty)
- 1.5 A (240 V AC, only pilot duty)
- Rated Current per Group (Max.): 8 A
-
Lamp Load (Max.):
- 200 W (230 V AC), 30 W (24 V DC)
- Spark Suppression with Inductive AC Loads: Must be performed externally according to driven load specification
-
Switching Frequencies:
- With resistive loads: Max. 1 Hz
- With inductive loads: On Request
- With lamp loads: Max. 1 Hz
- Output Type: Non-protected
- Rated Protection Fuse: 5 A fast
- Short-Circuit-Proof / Overload-Proof: No, should be provided by an external fuse or circuit breaker
- Overload Message: No
- Output Current Limitation: No
- Connection of 2 Outputs in Parallel: Not possible
- Lifetime of Relay Contacts (Cycles): 100,000 at rated load
-
Max. Cable Length:
- Shielded: 500 m
- Unshielded: 150 m