AI561 | ABB | Analog Input Module

SKU: AI561
  • Manufacturer: ABB

  • Product No.: AI561

  • Condition:في الأوراق المالية

  • Product Type: Analog Input Module

  • Product Origin: Switzerland

  • Payment:T/T, Western Union

  • Weight: 120g

  • Shipping port: Xiamen

  • Warranty: 12 months

Ordering Data

  • Part No.: 1TNE 968 902 R1101
  • Description: AI561, analog input module, 4 AI, U/I
  • Product Life Cycle Phase: Active

Technical Data

  • Process Supply Voltage L+: 24 V DC
  • Current Consumption via L+ Terminal: 0.1 A
  • Inrush Current (at Power Up): 0.05 A2s
  • Max. Ripple: 5%
  • Protection Against Reversed Voltage: Yes
  • Protection Fuse for L+: Recommended
  • Current Consumption from 24 V DC Power Supply: Ca. 10 mA
  • Galvanic Isolation: No
  • Surge-Voltage (Max.): 35 V DC for 0.5 s
  • Max. Power Dissipation Within the Module: 2.7 W
  • Weight: Ca. 120 g
  • Mounting Position: Horizontal or vertical
  • Cooling: Natural convection cooling must not be hindered by cable ducts or other parts in the control cabinet

Technical Data of the Analog Inputs

  • Number of Channels per Module: 4 individually configurable voltage or current inputs
  • Distribution of Channels into Groups: 1 (4 channels per group)
  • Resolution:
    • Unipolar Voltage: 0 V ... +5 V; 0 V ... +10 V: 12 bits
    • Current: 0 mA ... 20 mA; 4 mA ... 20 mA: 12 bits
    • Bipolar Voltage: -2.5 V ... +2.5 V; -5 V ... +5 V: 12 bits (including sign)
  • Connection of the Signals I0- to I3-: Terminals 3, 6, 9, 12
  • Connection of the Signals I0+ to I3+: Terminals 2, 5, 8, 11
  • Input Type: Differential
  • Galvanic Isolation: No galvanic isolation between the inputs and the I/O bus
  • Common Mode Input Range: Signal voltage plus common mode voltage must be within ± 12 V
  • Indication of the Input Signals: No
  • Channel Input Resistance:
    • Voltage: > 1 MW
    • Current: Ca. 250 W
  • Conversion Error of the Analog Values:
    • Voltage: Typ. ± 0.5 % of full scale
    • Current (0 mA ... 20 mA): ± 0.5 % of full scale
    • Current (4 mA ... 20 mA): ± 0.7 % of full scale
    • Max.: ± 2 % of full scale (all ranges) at 0 °C ... +60 °C or EMC disturbance
  • Time Constant of the Input Filter:
    • Voltage: 300 µs
    • Current: 300 µs
  • Analog to Digital Conversion Time: Typ. 500 µs per channel
  • Unused Inputs: Can be left open and should be configured as "unused"
  • Input Data Length: 8 bytes
  • Overvoltage Protection: Yes, up to 30 V DC only for voltage input
  • Max. Cable Length (Conductor Cross Section > 0.14 mm²):
    • Unshielded Wire: 10 m
    • Shielded Wire: 100 m
معلومات الطلب والضمان

شروط الشراء والإرجاع

إرشادات مفصلة حول الحد الأدنى لكمية الطلب ومواعيد التسليم وخيارات الدفع والضمان وسياسات الإرجاع.

نحن نقبل بكل سرور الطلبات بالجملة، مع الحد الأدنى لكمية الطلب وهو وحدة واحدة فقط.

عند الطلب، يمكننا تقديم جميع المستندات اللازمة، بما في ذلك شهادات المنشأ/المطابقة وغيرها من أوراق التصدير المطلوبة.

نحن نقبل الدفع بنسبة 100% T/T (التحويل البرقي) قبل الشحن. بالنسبة للعناصر التي تتطلب مهلة زمنية، يلزم إيداع 30% مقدمًا، مع دفع 70% المتبقية قبل الشحن. بالنسبة للتحويلات بالرنمينبي، يرجى الاتصال بنا إذا كان لديك وكيل في الصين.

جميع العناصر الجديدة والأصلية تأتي مع ضمان قياسي لمدة عام واحد. للحصول على خيارات الضمان الممتد، لا تتردد في الاتصال بنا للحصول على تفاصيل التسعير.

نحن نعطي الأولوية لرضاك. إذا كنت بحاجة إلى إرجاع منتج ما، فيجب أن يتم ذلك خلال 30 يومًا من تاريخ الشراء. يجب أن يكون المنتج غير مستخدم، وغير مفتوح، وفي عبوته الأصلية، بما في ذلك جميع الملحقات. ستتم معالجة المبالغ المستردة خلال 5-7 أيام عمل من استلام المرتجع. يرجى ملاحظة أن رسوم الشحن والمناولة غير قابلة للاسترداد.

مقارنة السلعة