HIMA|F3300|8-Fold Output Module
Description:
HIMA F3300 is an 8-fold output module designed for safety-related applications, supporting resistive or inductive loads up to 500 mA (12 W) and lamp connections up to 4 W.
Features:
- Integrated safe isolation and automatic testing during operation.
- Ensures no output signal with L- supply break.
Technical Specifications:
- Output Current: 500 mA per channel, short-circuit proof.
- Internal Voltage Drop: Max 2 V at 500 mA load.
- Admissible Line Resistance: Max 11 Ω (in + out).
- Undervoltage Tripping: ≤ 16 V.
- Short Circuit Current Operating Point: 0.75–1.5 A.
- Output Leakage Current: Max 350 µA.
- Test Signal Duration: Max 200 µs.
- Space Requirement: 4 TE.
- Operating Power: 5 V DC (110 mA), 24 V DC (180 mA additional load).
- Cable: LiYY 8 x 0.5 mm² or 16 x 0.5 mm².
- Diode: 1N4007 or 1N4448.
HIMA|F3300|8-Fold Output Module



HIMA|F3300|8-Fold Output Module
Description:
HIMA F3300 is an 8-fold output module designed for safety-related applications, supporting resistive or inductive loads up to 500 mA (12 W) and lamp connections up to 4 W.
Features:
- Integrated safe isolation and automatic testing during operation.
- Ensures no output signal with L- supply break.
Technical Specifications:
- Output Current: 500 mA per channel, short-circuit proof.
- Internal Voltage Drop: Max 2 V at 500 mA load.
- Admissible Line Resistance: Max 11 Ω (in + out).
- Undervoltage Tripping: ≤ 16 V.
- Short Circuit Current Operating Point: 0.75–1.5 A.
- Output Leakage Current: Max 350 µA.
- Test Signal Duration: Max 200 µs.
- Space Requirement: 4 TE.
- Operating Power: 5 V DC (110 mA), 24 V DC (180 mA additional load).
- Cable: LiYY 8 x 0.5 mm² or 16 x 0.5 mm².
- Diode: 1N4007 or 1N4448.